我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
P5 relay can not communicate with PC if its IP address is in a 90.xx.xx.xx subnet range

Issue summary:

The issue which P5 cannot communication with another device occurs when the customer’s device is configured with IP address in the 90.xx.xx.xx range and subnet mask 255.0.0.0.
The detailed explanation:

the P5 relay’s mini-USB port is set to IP 90.0.0.1 and a subnet mask of 255.0.0.0. When the PC with IP address 90.xx.xx.xx sends a ping to the P5 relay, the P5 relay interprets this as being on the same subnet as the USB port. It then attempts to send the response through the USB interface instead of the rear ethernet port where the request was actually received. This prevents the PC from properly communicating with the P5 relay via the rear ethernet port.

Proposed Solutions:
•    Suggest changing the customer’s IP address range to avoid starting with 90.x.x.x, ensuring it doesn’t conflict with the USB interface.

Action for prevent future occurrence:
•    Update the user manual to include a limitation: “The P5 relay’s IP address must not start with ‘90’ due to conflict with the USB interface.”
•    Implement a firmware limitation in the tool: Block the user from setting an IP address starting with 90 to prevent this issue occurring.

Please contact the P5 Technical Support if you are still having problems connecting to your relay.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings