我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How do I run a battery test from the Web Interface in my Galaxy VS?

Issue: ​

Customers would like to use the web interface to run a battery test remotely.

Product Line:​

Galaxy VS

Environment:​

Galaxy VS (All versions)

Cause:​

Battery test is not available in the web interface

Resolution:​

The Remote Battery Test feature has been introduced in Firmware revision 6.118.3.171 (Released in May 2025) and is also available in higher versions. However, this function is not available by default in the UPS configuration.

This feature has to be enabled from the UPS display by following the path Configuration -- Battery -- Go to the second screen -- Battery Self-test allow remote control and checking the box.

Battery Configuration screen for Remote Battery Test



Once the setting is accepted, log in to the web interface. You will be able to see a new tab called Tests, where you can start a remote battery test.

Screen after enabling the remote battery test

Important note: Our commitment is to deliver secure products, utilizing secure development processes, and reliable update management; therefore, firmware upgrades can only be performed by Schneider Electric-qualified personnel during maintenance visits (repair or PM) and will not be posted on the website.

Secure NMC System for 3-Phase products can be consulted for further questions.

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings