PME - "Unable to start VIP Modbus Slave Communication" error

Issue

A VIP with Modbus Slave Modules has been set up with a slave port added under Management Console > Tools > System > ION Virtual Processor Setup. The following error appears in the Management Console > System Log Events: "Unable to start VIP Modbus Slave communication. A license is required to use the VIP Modbus Slave feature."

Unable to start VIP Modbus Slave communication error

Product Line
Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment

VIP Modbus Slave


Cause 1

The VIP Modbus Slave feature requires the additional Data Exchange Module license, which isn't activated on the system.


Resolution 1

Confirm there is an active Data Exchange Module license shown in License Configuration Manager:

Data exchange module

Cause 2

On PME 2021 or later, the service for the VIP with the Modbus Slave Modules is starting before the licensing service starts, causing it to not recognize the Data Exchange Module license and not initialize the Modbus Slave feature.

Resolution 2

1. Open Services and locate the ION Virtual Processor Service associated with the VIP that has Modbus Slave Modules

2. Right-click on the service > Properties

3. Set the Startup Type to "Automatic (Delayed Start)"

4. Restart the service

automatic delayed start service properties

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings