我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Power Quality Reports are not working and showing "An Unexpected error has occurred"

Issue

Power Quality Reports are not working and showing "An Unexpected error has occurred"

Product Line

Power Monitoring Expert 7.2.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment

Power Monitoring Expert Software Configuration

Cause

System logs in Management Console show errors stating " Groups already has a rate of…. Group can only have one rate…Please fix this and run the import"

This is caused when the PowerQuality.csv contains multiple rates

Resolution

*Warning: Take backups of any files prior to modifying them.  Ensure the backups are in a location that will not be overwritten (i.e. the Desktop)

1.)  Locate the  PowerQualityGroups.csv file which is located under the folder : {root install folder}\Applications\Power Quality\

2.)  Make sure there is only one rate under Column E as per the following guide

PowerQualityGroup.csv

Please see the following guide for reference to the PowerQualityGroup definitions and configuration

Edit PowerQualityGroup.csv

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings