SAGE Offline Editor (v2.1.0.4) — No “Save/Save As” When Migrating C3413 Configuration to C3414

Issue:
When creating a new configuration for a C3414 based on an older C3413 configuration, the customer reports there is no “Save” or “Save As” option—only “Restore Backup” and “Set RTU Type.” They ask if they must convert the configuration to the latest firmware before editing in the Offline Configurator.

Product:
SAGE RTU Offline Configuration Editor (version 2.1.0.4); SAGE CPU modules C3413 and C3414.

Environment:

  • Offline editing of an existing C3413 configuration to target a C3414
  • Using Offline Editor v2.1.0.4
  • UI shows only “Restore Backup” and “Set RTU Type” (no “Save/Save As”)

Cause:
In the latest revisions of the Offline Editor, changes are auto‑saved on the fly and the explicit “Save/Save As” buttons were removed. When you close the Offline Editor, it finalizes all edits and writes them to the configuration file. The editor also creates a backup of the original configuration file that was opened.

Resolution:

  1. Proceed with edits normally—the Offline Editor auto‑saves as you work.
  2. Close the Offline Editor to terminate the edit session and commit all changes to the configuration file; a backup of the original is created automatically.
  3. Verify persistence: Re‑launch the Offline Editor, open the same configuration file, and confirm that all prior edits are present.
  4. To target the new hardware, use “Set RTU Type” to change from C3413 → C3414 within the editor.
  5. No separate firmware conversion step is required just to enable saving; however, ensure the Offline Editor revision you’re using supports the target CPU/firmware. If there are firmware‑specific features, use the corresponding editor revision or consult support for compatibility guidance.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings