PME - Reports error when clicking Select Sources "An unexpected error has occurred"

Issue

When selecting sources or measurements in a report, it shows "An unexpected error has occurred".

Reports error

Checking the log under Settings tab > System > System Log shows the following error: "Validation of viewstate MAC failed. If this application is hosted by a Web Farm or cluster, ensure that <machineKey> configuration specifies the same validationKey and validation algorithm. AutoGenerate cannot be used in a cluster."

Validation of viewstate MAC failed error

Product Line
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment

Reports


Resolution

1. On the PME server, open File Explorer and navigate to ...\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\SystemDataService

2. Make a copy of the existing web.config file and place it in a separate backup folder

3. Open the web.config file in Notepad, then deleted the below highlighted text:

Delete cookieSameSite="None" requireSSL="true"

4. Save the web.config file
5. Navigate to ...\Program Files (x86)\Schneider Electric\Power Monitoring Expert\web
6. Make a copy of the existing web.config file and place it in a separate backup folder
7. Open the web.config file in Notepad, then deleted the below highlighted text:

Delete cookieSameSite="None"

8. Save the web.config file
9. Open the Windows Start menu and search for "cmd", then right-click > Run as Administrator
10. Type "iisreset" (without the quotes) and press Enter to run the command
11. Open the Windows Start menu and search for "Services"
12. Restart the ION ApplicationModules Core Services Host Service

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings