The Critical Byte Order Setting When Integrating SCADAPack x70 with Geo SCADA Expert

Geo SCADA Expert offers flexibility in communicating with SCADAPack controllers through a selection of drivers. The specific driver required is determined by the type of SCADAPack device(s) in use.

When using the Modbus protocol for communication, it is crucial to consider byte ordering for correctly interpreting 32-bit floating-point values. Depending on the chosen Geo SCADA Expert driver, you may need to adjust the byte ordering configuration in the RemoteConnect software to ensure the correct values are displayed.

The necessity of changing the byte order setting is entirely dependent on the specific driver used in Geo SCADA Expert:

  • SCADAPack x70 with Advanced Modbus SCADAPACK Direct Driver:
    • If you are using a SCADAPack x70 as an outstation and select the Advanced Modbus SCADAPACK Direct outstation driver in Geo SCADA Expert, you must change the byte order in RemoteConnect.
    • The RemoteConnect setting needs to be changed from the Default setting of 3412 to 1234.

ScadaPack

ByteOrder

  • Conversely, if you utilize the more Generic  Advanced Modbus driver in Geo SCADA Expert, no change to the byte order in RemoteConnect is typically required.

Generic

Default

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings