Serial Port Pinout for SAGE RTU 3030 Model

Issue

Users need the correct RS-232 DB9 pinout for the SAGE 3030X serial ports to ensure proper wiring and communication with IEDs and other devices.

Product

SAGE RTU 3030 / 3030M

Environment

Utility substations using SAGE 3030X for SCADA and automation, connecting to Intelligent Electronic Devices (IEDs) or Master Terminal Units (MTUs) via RS-232 serial ports.

Cause

Incorrect pin assignments during installation can lead to communication failures, loss of data, or inability to synchronize timing signals.

Resolution

The SAGE 3030X rear panel includes 16 RS-232 serial ports (DB9 connectors) plus one PPP port. The pinout for these ports is as follows:

Signal

Pin #

Description

Type

DCD

1

Data Carrier Detect*

Input

PWR

1

+5V for aux devices*

Output

RX#

2

Receive Data

Input

TX#

3

Transmit Data

Output

IRIGB

4

Timing Signal

Output

DGND

5

Ground

N/A

IRIG_GND

6

IRIG Ground

N/A

RTS

7

Request To Send

Output

CTS

8

Clear To Send

Input

RI

9

Ring Indicator

N/A

Notes:

  • Pin 1 can be configured for either DCD or +5V power output (default is DCD).
  • IRIG-B timing signal is available on Pin 4, with ground on Pin 6.
  • RS-232 power (5VDC) is selectable on all 16 ports, max 5W total.
  • Use proper shielded cables for IRIG-B and serial connections.

For front panel Console and PPP ports, the pinout differs slightly (includes DTR and DSR signals).

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings