我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to generate a list of DNP3 or Modbus - Advanced points with historic enabled

It might be helpful, for maintenance purposes, to have a list of points that have the “Historic” option enabled. Below are two queries that can be used to generate such lists for DNP3 points and Modbus – Advanced points respectively:

SELECT

ID, FULLNAME

FROM

CDNP3POINT

WHERE

( "Historic" = TRUE )

ORDER BY

"FullName" ASC

----------------------------------------------

SELECT

ID, FULLNAME

FROM

CADVMODBUSPOINT

WHERE

( "Historic" = TRUE )

ORDER BY

"FullName" ASC

Please note that similar queries can be used to generate lists for other drivers. Proper tables for each driver can be found by using the Database Schema. More information on how to use the Database Schema can be found int the manual.

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings