How to use "Short Pulse" and "Long Pulse" command on BMXNOR0200H RTU module ?

Issue:

How to use "Short Pulse" and "Long Pulse" command on BMXNOR0200H RTU module ?

Product Line:

BMXNOR0200H RTU module.

Environment:

EcoStruxure Control Expert, Windows 10

Resolution:

To use the Short Pulse command, ensure that the same variable type (C_SC) is configured on both client and server side, with identical IOA settings.

Additionally, the pulse duration must be defined on the server.

EXAMPLE: Using 2 BMXNOR0200H modules:

  • Server IP: 192.168.30.1
  • Client IP: 192.168.30.2

We will configure a variable on both the server and client side, with "Type Identification" set to C_SC and "IOA" set to 2.

On the server, the "Short Pulse" duration will be configured to 100 ms.

SERVER:

Screenshot1

Screenshot2

CLIENT:

Screenshot3

Using a configuration where both the client and server variables are set with Type Identification = C_SC and IOA = 2, and the server's 'Short Pulse' duration is configured to 100 ms:
When the client variable command1.Value changes from 3 to 1, the server variable commande_server.Value will activate for 100 ms, then automatically return to its initial state.

Screenshot4

A network capture performed with the Wireshark tool confirms the communication exchanges between the server and the client :

Screenshot5

This behavior can be validated using the Trend tool in EcoStruxure Control Expert, which provides a visual confirmation of the temporary change in the server variable:

Capture 7

Details of the command to be send:

The example below using "Command.Value" variable:

  • To send a command, we need to trigger the value of the low byte (8 bits) of the %MW register.
  • The value to be transmitted is the value of the lowest bit of this %MW register :

capture10

The point size of C_SC_NA point is 1 bit, as detailed below :

capture20

The command result will be available in the "Command.Status" variable. For more details regardins its different values and their corresponding description, please refer to page 265 of the user manual:

Capture30

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings