我们今天能为您提供什么帮助?

My Smart UPS Modular Ultra has an Unknown UPS internal error (1568-00B0) or Unknown UPS internal error (156A-00B0) alarm.

Purpose:

If you update your UPS to FW 15.0 or later and you have an SBU (Service Bypass Unit) connected, you may see an Unknown UPS internal error (1568-00B0) or Unknown UPS internal error (156A-00B0) alarm.


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers on UPS Firmware 15.0 or later with an SBU (Service Bypass Unit) connected.


Resolution:

UPS Firmware 15.0 and greater supports new events for the SBU switch positions.  In order to see the correct alarm messaging on the display and NMC, please upgrade the NMC/Display to the latest firmware.  See below for FAQs on the different ways to upgrade that firmware.

How to Install the Smart-UPS Modular Ultra NMC/Display Firmware using the USB Port
Web link - https://www.apc.com/us/en/faqs/FAQ000261841/

How do I update my Smart-UPS firmware using the web interface of my Network Management Card?
Web Link - https://www.se.com/ca/en/faqs/FA170679/

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings