我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to access a Bit in a WORD variable in EcoStruxure Operator Terminal Expert?

Issue:

Alternative to access directly a bit of a WORD, without creating a BOOL type variable pointing to this specific bit.

Product:

EcoStruxure Operator Terminal Expert v3.x , v4.x (EOTE)

Environment:

HMI Configuration Software in Windows

Resolution:

Option 1: Define a BOOL variable that points to a specific bit of a WORD.

1

Note: This requires creating a new variable for each bit you need.

Option 2: Use a custom script to automatically create multiple variables. If adapted, the same script can be reused for several variables.

Part of the script:

2

Result:

3

Attached Resources:

  • EOTE Project: Minimum version v3.5 required to open.
  • Control Expert Project: Minimum version v15.1 required.
  • Video: Demonstrates the final result.

施耐德電機Taiwan

附件
FAQ000279923.zip [18.02 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings