Basic Troubleshooting for Secure Viewer Thin Client in Machine SCADA Expert v2023

Article available in these languages:

  • 西班牙文

Issue:

When working with Thin Clients in Machine SCADA Expert, setting up the Secure Viewer Thin Client and ensuring proper functionality can sometimes be challenging. This FAQ covers general checks and recommendations.

Product:

EcoStruxure Machine SCADA Expert v2020, v2023

Environment:

HMI Configuration Software in Windows

Resolution:

If you encounter issues getting Secure Viewer to work, follow these steps:

1- Verify License Limits

Confirm the number of parallel Thin Clients allowed by your license and ensure you do not exceed this limit.

1

2- Check Network Ports

Make sure port 1234 or 51234 (encrypted) is open on the Thin Client machine.

3- Enable Only One Port

Ensure that only one port is enabled at a time and configure this port in the Secure Viewer settings screen.

2

3

4- Validate Your Configuration

Validate your Secure Viewer configuration by following the steps shown in this video for AVEVA Edge (same product):

https://www.youtube.com/watch?v=CqV0s5YYhzk&t=1372s

If problems persist, please contact your local technical support team.

Related resources:

Title: EcoStruxure™ Machine SCADA Expert, Help Manual

URL: https://download.schneider-electric.com/files?p_Doc_Ref=EIO0000002448&p_enDocType=User+guide&access=Public

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings