HMIST6500, Operator Terminal Expert - Time limit for the clock setting.

Issue:

Why is there a limit for the clock setting. This means that passed Jan 18-2038 the clock will stop functioning?

Time limit on key entry.

Product Line:

EcoStruxure Operator Terminal Expert (all versions), All Harmony, non Windows HMI.

Resolution:

In the EcoStruxure Operator Terminal Expert help, we can fins the below information in regards to the maximum limit on the date and time.

Help section about the time limit.

This is related to the Year 2038 problem. See below the Wikipedia link on this subject for more information.

https://en.wikipedia.org/wiki/Year_2038_problem

R&D provided the more specific information in regards to this problem and a potential workaround:

The 2038 is the maximum value of UNIX time.

If this value is exceeded, an overflow will occur, causing the time to stop or the value to reset to 0 and return to 1901,

which could cause the system to malfunction.

Basically no workaround, by 2038 the development team will usually plan to change, design the software to support 2038 and beyond (e.g. support to 64 bit).

For now, there is no plan for this requirement.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:

需要協助?

需要協助?

產品選型工具

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

支援中心

在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings