BCIM Functionality Requirements with Micrologic Active
Make sure to use EPC 2.39 or above to upgrade Micrologic Active trip unit toFirmware version 004.004.003 or later
What happens if the Micrologic Active firmware is not updated?
You may experience issues such as:
-
BCIM not appearing in the EPC
-
Incorrect or missing measurement data
-
Communication errors on the trip unit
Note : Ensure 24V auxiliary supply provided to BCIM separately through the 6-Pin COM port.
發佈於: 施耐德電機Taiwan
需要協助?
產品選型工具
快速輕鬆地為您的應用找到合適的產品和附件。
取得報價
立即線上提交您的銷售需求,專業團隊將主動聯繫您。
購買地點
輕鬆在您所在地區找到最近的施耐德電機經銷商。
支援中心
在同一位置找到滿足您所有需求的支援資源。