Easergy Studio Project Structure and Warning When Opening Project File

Article available in these languages:

  • 西班牙文

Issue

When opening an Easergy Studio project file (.sestudio), a warning message appears indicating that the project data cannot be found or is incomplete.

Product

MiCOM Px20, Px30, Px40

Easergy Studio Software

Environment

All versions of Easergy Studio using project files with extensions:
.sestudio (formerly .studio)
.sestudioarch (formerly .studioarch)

Cause

An Easergy Studio project is composed of two required elements:

1.Project index file

  • File extension: .sestudio
  • Acts as the main reference file for the project

2.Project folder

  • Has the same name as the .sestudio file
  • Contains all relay settings, configurations, and record files associated with the project

The warning occurs when the .sestudio file is opened without its corresponding project folder. Since the folder contains all the actual project data, Easergy Studio cannot locate the necessary files and triggers a warning.

Resolution

To resolve the issue, apply one of the following solutions:

1.Ensure correct project structure

  • Verify that the .sestudio file and its corresponding folder are located in the same directory
  • The correct structure should appear as:
    New System.sestudio
    New System_sestudio (folder)

2.Use the exported project archive (recommended best practice)

  • Export the project using the Export Project function in Easergy Studio
  • This creates a single compressed file with extension:
    .sestudioarch
  • Share this archive instead of separate files

3.Import the archive properly

  • Import the .sestudioarch file into Easergy Studio
  • The software will automatically extract and rebuild the correct project structure

Note: The .sestudioarch file is a packaged archive containing both the project index file and its associated folder.

1

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings