PowerChute is flagged as vulnerable to CVE-2026-91403

Issue:

PowerChute has been flagged as vulnerable to CVE-2026-91403

Products:

PowerChute Serial Shutdown 1.6

PowerChute Network Shutdown 5.2

Environment:

All support operating systems

Cause:

PowerChute ships with OpenJDK version 21

Solution:

Update the Java that PowerChute uses to version 21.0.13+9. You can download the latest OpenJDK from this link.

https://adoptium.net/temurin/releases?version=21&os=any&arch=any

1 - After downloading the latest version, to update the PowerChute Java navigate to the PowerChute folder/directory and create a new folder/directory named Updates.

The default path for PowerChute on a Windows system is:

C:\Program Files\APC\PowerChute for PowerChute Network Shutdown

Updates folder on a Windows system

C:\Program Files\APC\PowerChute Serial Shutdown for PowerChute Serial Shutdown

PowerChute Serial Shutdown update folder

On Linux, the default path is:

/opt/APC/PowerChute for PowerChute Network Shutdown

Updates directory on for PCNS on Linux system

/opt/APC/PowerChuteSerialShutdown for PowerChute Serial Shutdown

Updated directory for PCSS on Linux

2 - Copy the Windows .zip or Linux .gz file to Updates folder/directory created at step one.

3 - Log in to the PowerChute web UI and go to About and scroll down to the Java version information you will see the available Java update information. Click the Update java button then click OK.

PowerChute Network Shutdown

About menu for PCNS

PowerChute Serial Shutdown

Update java on PCSS

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings