ION Setup - "Network configuration seems corrupted" error

Issue

After logging into ION Setup, the following error messaged is displayed: "Network configuration seems corrupted. Do you wish to load the backup copy?"

Network configuration seems corrupted

Product Line

ION Setup

Cause

Due to a previous crash, interruption, or unsuccessful save, the network configuration files can sometimes become corrupted.

Resolution 1

Click Yes to see if it successfully loads the network configuration.

Resolution 2

If there is access to an existing Power Monitoring Expert (PME) 2020 or later installation, refer to this article to import the device list from PME.

Resolution 3

Try looking for manual backups of the network configuration files:

  • In File Explorer, go to View > check Hidden Items:

Hidden Items

  • Look for renamed copies of DEVINFO.DAT, IONSETUP.DAT, and SITEINFO.DAT. There may be some present in manually created folders in the C:\ProgramData\Schneider Electric\ION Setup folder or in other folders/drives. To restore:
    • Close ION Setup.
    • Move the files to the C:\ProgramData\Schneider Electric\ION Setup folder.
    • Rename the files to DEVINFO.DAT, IONSETUP.DAT, and SITEINFO.DAT respectively.

Resolution 4

Manually recreate the device network. To facilitate this:

  1. Manually add one device of each type, and at least one Ethernet site and one Ethernet Gateway site (if applicable). Refer to this article for the steps to add a device.
  2. Open File > Export Network.
  3. Open the exported .csv using Excel.
  4. Use Excel to populate the list with remaining devices and/or sites, following the formatting of the exported .csv.
  5. Save the .csv and close Excel.
  6. In ION Setup, open File > Import Network.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings