{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Video: How can I get a run status on ATV212?
Issue:
Programming RY Relay for Run Status on ATV212 Drives.

Product line:
Altivar 212

Environment:
All models, all serial numbers

Cause:
Need for a signal from the drive indicating that the motor is running.

Resolution:
Wire to RYA and RYC relay and program F130 to 14 (drive running).  The relay will close if a run command is issued and there are no faults.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: