How can we help you today?

Can a Modbus protocol be used to communicate between a Micrologic and a TSX PLC?

Yes, Modbus communication is possible between a Micrologic and a TSX PLC.  For an NT, NW or compact NS 800 to 3200 plug-in circuit breaker, the data tables are divided into 4 managers (3 for a fixed circuit breaker).

The four addresses (or the 4 slaves with linked addresses) are:

  • @ xx for the circuit breaker manager
  • @ xx +50 for the "chassis" manager
  • @ xx +100 for the "protection" manager
  • @ xx +200 for the "measurement" manager

Example:  A circuit breaker configured with address 21 has the circuit breaker manager at address 21 and the measurement manager at address 221, etc.  For communication with a PLC, the module used must be capable of managing the addresses up to 247.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.