Why does the PM5110 (METSEPM5110) meter display incorrect power readings or not show any current?

The connections from S1 and S2 on the current transformer to I+, and I- on the back of the meter might be reversed, ensure that the wiring of the meter is correct as per the user manual

Incase of using a stand alone CTs, ensure the P2 is facing the load

Ensure that the meter has been programmed (e.g CT ratio , System Type)

S1 and S2 connections may still have the link in, (Please remove this while power is OFF)

Please note that this relates to all Meters from the Power Logic PM5000 range.

The link to this range on our website is shown below:

https://www.se.com/uk/en/product-range/61281-powerlogic-pm5000/?parent-subcategory-id=89024129&filter=business-2-building-automation-and-control