Is it possible to join 2 single phase Acti9 distribution boards on top of each other?
It is not possible to join 2 single phase distribution boards on top of each other as we do not offer a joining kit
Solution:
It is possible to join three phase boards on top of each other, depending on the number of ways required. You could use 2 x Three phase Acti9 Distribution boards, single phasing kits and then use the joining kit to suit
e.g. For 2 x 6 Way boards on top of each other you would use the below
SEA9BPN6 x 2 (6 Way Three Phase Distribution Board)
SEA91253N x 2 (125A Switch for both boards)
SEA9P125SPKIT x 2 (Single phasing kit allowing you to feed all busbars in the Distribution Board with a single phase)
SEA9BNTJKN x 1 (This is the Joining Kit required)