{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What needs to be done to the ATV320 drive if you are using a ungrounded IT system?

Article available in these languages: Spanish

Issue:
ATV320 needs to use unground IT systems

Product Line:
Altivar Machines, Altivar 320

Environment:
All models and serial numbers

Cause:
IT ungrounded system

Resolution:
See the attached document IT grounding ground screw removal.pdf for the 230V drives, 400/460V B version drives and 400/460V C  version drives 4.0 kW and smaller.
For ATV320U55N4C - ATV320D15N4C see attached document IT_Jumper_ATV320_N4C.pdf

Schneider Electric UK

Attachment(s)
IT grounding ground screw disable.pdf [942.97 KB]
IT Jumper_ ATV320_N4C.pdf [315.15 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: