How can we help you today?
What is the operating time of ground fault protection devices defined in the UL 1053 standard?
The UL 1053 standard defines in Table 22.1 the operating time of the ground fault protection devices:
| Ground-fault current (A) | Time (s) |
| 85% of pickup current | Shall not trip |
| 115% of pickup current | Ultimately |
| 150% of pickup current | 2 |
| 250% of pickup current | 1 |
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.