Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What classes of fuses do the DT321 and DT321RB safety switches accept?
Issue:
Fuse data

Product Line:
Safety switches

Resolution:
These switches accept class H or K fuses as standard. Options include class R fuses (field install class R fuse kit). With Class H or K fuses installed, the switches are UL listed for use on systems with up to 10,000 RMS symmetrical amperes available fault current. With class R fuses (and class R fuse kit installed), the switches are UL listed for use on systems with up to 200,000 RMS symmetrical amperes available fault current.
NOTE: DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability, and will void the warranty.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings