Does a QO200TR provide overcurrent protection?​

Issue:
Will the QO200TR provide overcurrent protection?

Product Line:
Molded Case Switch

Environment:
Enclosed Molded Case Switch

Resolution:
No, this is a molded-case switch with no overcurrent protection. For a similar device with overcurrent protection, consider using the circuit breaker enclosure QO2TR and a QO 2-pole circuit breaker up to 60 amperes maximum. The QO2TR is suitable for use on 240Vac maximum applications only. There is no neutral assembly supplied with or available for the QO2TR; therefore, it is not suitable for 120/240Vac applications. The QO2TR will not accept a QO-GFI, QO-EPD, or QO-AFI circuit breaker.