Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you short out a neutral CT for NT, NW, P or R breakers when it is installed, but you don`t want to use it? Do jumpers need to be added?
Issue:
Sometimes an installed circuit breaker is connected to an installed neutral CT, and there is a need to disconnect the NCT wires from the breaker, but the neutral CT cannot be physically removed from the equipment. When the NCT wires are disconnected, is there a need to add any jumpers to the NCT terminals?

Product Line:
Circuit Breakers

Environment:
Applies only to Masterpact NT, NW, and PowerPact P and R circuit breakers

Resolution:
For Masterpact NT, NW, or PowerPact P or R Circuit Breaker with neutral CT already installed, in order to disconnect the NCT from the breaker without removing the NCT from the equipment, follow these steps:

NEUTRAL CT'S WITH TERMINALS LABELED T1, T2, T3, T4
(1) De-energize the equipment
(2) NCT terminals
  • Remove the wires from NCT terminals T1 and T2 (there is no need to jumper those terminals)
  • Make sure there is a jumper between NCT terminals T3 and T4
(3) Circuit Breaker terminals (green connector on top of the trip unit)
  • Remove the wires from breaker terminals T1 and T2, and ADD A JUMPER between breaker terminals T1 and T2
  • Do NOT add add a jumper between breaker terminals T3 and T4

OLDER NEUTRAL CT'S WITH TERMINALS LABELED SG1, SG2, X1 and X2
(1) De-energize the equipment
(2) NCT terminals
  • Remove the wires from NCT terminals SG2 and SG1 (there is no need to jumper those terminals)
  • Make sure there is a jumper between NCT terminals X1 and X2
(3) Circuit Breaker terminals (green connector on top of trip unit)
  • Remove the wires from breaker terminals T1 and T2, and ADD A JUMPER between breaker terminals T1 and T2
  • Do NOT add add a jumper between breaker terminals T3 and T4

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings