Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
The Buck Boost Calculator slide chart has a lowest voltage listed. What happens if voltage varies above or drops below that value?

Issue:
Voltages lower or higher than the range of available Buck Boost Calculators

Product Line:
LV Transformers

Environment:
Applies to Buck Boost Transformers by SquareD/Schneider Electric

Cause:
Buck Boost Transformers offer a specific percentage of voltage increase or decrease, but within a set range

Resolution:
Should the voltage drop below the listed value, the connection will still provide the same voltage ratio change (provided that the voltage does not drop below the point necessary to excite the core of the Transformer.) However, it is important to remember that a Transformer is a current rated device. Thus, the Autotransformer connection is current rated as well. So, if the voltage drops and the current rating remains fixed, then the overall kVA capacity of the Autotransformer connection drops proportionately.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings