Video: Can the operating handle of a Heavy Duty safety switch be padlocked in the ON or OFF position?

Article available in these languages: Spanish

Issue:
Product Features

Product Line:
Safety Switch

Environment:
Product features

Cause:
Verification

Resolution:
Lock OFF:
Provision to padlock the operating handle in the OFF position is standard on all Heavy Duty safety switches.
Lock ON:
There are two methods to provide provisions to padlock the handle in the ON position (subject to local code regulations - consult local authorities for interpretation):
(1) As a factory option on some heavy duty safety switches, add suffix SPLO to the standard catalog number. This may be added to 30-1200 A, NEMA 4/4X/5 stainless steel, 12, and 12K switches. This provision will allow the customer to use one 3/8" maximum hasp padlock to lock the switch in the ON position. Check the latest Square D Digest for the price adder.

(2) Modifying a switch in the field may be done to the 30 - 200 ampere, Series F switches, all NEMA types, and to our 400 - 1200A switches, Series E, all NEMA types. The lockplate on the side of the switch next to the handle has a very small indentation (a center punch) towards the top of the lockplate, which may be drilled out to accommodate a padlock. Note that drilling a hole in the steel of our painted devices will expose unpainted steel, which should be touched up with paint. Our gray paint is in a spray paint can, catalog number PK49SP.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings