How is the motor operator for a PowerpacT P-frame breaker wired?

Issue:
How is an electrically operated P-frame breaker wired?

Product Line:
PowerPacT P-frames

Resolution:
B4 (hot) - A1 (common) to power the spring charging motor.
A4 (hot) - A1 (common) to open the breaker.
A2 (hot) - A1 (common) to close the breaker.
See attached wiring instructions from the catalog.

Schneider Electric USA

Attachment(s)
P Frame Motor Wiring.pdf [683.13 KB]