Issue:
Change from automatic reset to manual reset on a TeSys overload.
Product Line:
IEC Contactors and Starters
Environment:
TeSys Overload Relays
Resolution:
There is a small tab to the right of the current adjustment dial under the clear cover. Break this tab off to reveal a small switch that is used for this adjustment. There is an H and A to designate the settings; H for Hand and A for Automatic.
CTA-ID : 2008074
Change from automatic reset to manual reset on a TeSys overload.
Product Line:
IEC Contactors and Starters
Environment:
TeSys Overload Relays
Resolution:
There is a small tab to the right of the current adjustment dial under the clear cover. Break this tab off to reveal a small switch that is used for this adjustment. There is an H and A to designate the settings; H for Hand and A for Automatic.
CTA-ID : 2008074