What is difference between Type NL (K-4 rated) or NLP (K-13 rated) Transformers compared to standard Low Voltage Distribution Transformers?
Issue:
K Rating on Low Voltage Transformers

Product Line:
LV Transformers

Environment:
Product sold in North America

Cause:
Harmonic Energy generation in Electrical Systems

Resolution:
SquareD/Schneider Electric`s line of K-rated transformers are designed to minimize the eddy current, or stray losses within the Transformer.  It is these eddy/stray losses that are affected by non-linear loads such as computers, fax machines, and other office electronic equipment. A k13 rated transformer will accommodate a higher level of harmonics without exceeding its temperature rating than a k4 rated unit of the same kVA, voltage and temperature class.
K rated Delta Wye units will operate at full load in circuits rich in harmonics without exceeding the temperature rating of their insulation systems.  Once the loading goes above 80% of transformer capacity and a high level of harmonics are present, k4 units should be considered to prevent overheating.  At loading levels above 90% a k13 unit should be used. The recommendation to use k Factor Transformers for computer loads assumes high harmonics and high loading levels.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings