Is the 2510K a suitable device for use in a lockout / tagout application?
Issue:
Does the 2510K work in a lockout / tagout application?

Product Line:
Manual Starters and Switches

Environment:
2510 Type K Manual Switches

Resolution:
The 2510KG2 is a UL508 controller, not a UL98 fusible or non-fusible disconnect switch nor a UL489 circuit breaker disconnect. As such, this device is not suitable for use as a lockout device.