Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can I run 4 preset speeds on the ATV28?
Issue:
Program Preset Speeds on the ATV28

Product Line:
ATV28

Environment:
All

Cause: N/A

Resolution:
Program LI3 for 2 Preset Speeds (PS4) and LI4 for 4 Preset Speeds (PS4) in the I-O Menu.
Speed number one will be made from your low speed (LSP) from menu #2 setting. It will run at LSP (or the speed determined by the analog inputs) if the drive has a run signal and if both preset speeds are inactive.
The second and third speeds are set the SEt menu at parameter SP2 & SP3. If there is a run command and only LI3 is active, the drive will run at the SP2 speed, and if only LI4 is active, it will run at the SP3 speed.
If there is run command and both of the preset speed inputs are active, the drive will run at high speed (HSP in the SEt menu)


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings