Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the terminal lug data for ALL of the 600amp, US and Canada, Heavy Duty Safety Switches(for example, H266,CH226N, CH326NDS, H326DS, H366, H366R, HU366, HU366AWK and CHU366AWK )?

Issue:
Product Feature

Product Line:
Safety Switch

Cause:
Wire installation

Resolution:
The U.S. 600Amp Heavy Duty Safety Switches will accept as standard (2) #3/0 AWG through 500 KCMIL aluminum or copper wires per phase. The Lug conductor(or wire) temperature rating is 75 degrees C.

The Canadian 600Amp Heavy Duty Safety Switches will accept as standard (1) 350 - 500kcmil AL or CU wire per phase OR        (2) 1/0 - 300kcmil AL or CU wire per phase. BUT it is always good to verify by checking the switch wiring diagram label.


NOTES:
1)
The only alternate lugs are compression lugs and they do NOT allow for any different wire size or quantity than what is shown above.
2) 90 degree wire can be used, BUT it MUST be sized per the 75 degree ampacity table in the National Electrical Code.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings