Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you select an HVL/cc Main Tie Main with Automatic Transfer in the center of the lineup with MotorPact starter feeders on each side?
Issue:
Selection

Product Line:
INMVE - MV EQUIPMENT

Environment:
NEMA ICS 3, UL347, EEMAC G14-1, ANSI C19.7, IEC 60470, IEC 60529, IEC60694, IEC60129, IEC62271-102, IEC 62271-200, ANSI C37.20.7

Cause:
A complex application requires careful consideration of layout.

Resolution:
To select an HVL/cc Main Tie Main with Automatic Transfer in the center of the lineup with MotorPact starter feeders on each side:

Put the voltage-sensing VTs in an incoming auxiliary section and have the cables come in there rather than into the main switches.

Choose the load side connection of the mains to be To Motorpact

CTA-ID : 2011870

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings