Issue:
Minimum panel depth and shaft length for vario switches
Product Line:
Motor Disconnect Switches
Environment:
Vario Switches
Resolution:
When rear mounting the switch a shaft extension is required. The minimum enclosure depth required is 5.5". The switch itself is approximately 2.56" so the shaft extension would be 2.96" minimum length.
Minimum panel depth and shaft length for vario switches
Product Line:
Motor Disconnect Switches
Environment:
Vario Switches
Resolution:
When rear mounting the switch a shaft extension is required. The minimum enclosure depth required is 5.5". The switch itself is approximately 2.56" so the shaft extension would be 2.96" minimum length.
Released for: Schneider Electric USA