Can an 8903LX mechanical held lighting contactor be manually latched or unlatched?
Issue:
How to unlatch the 8903LX mechanically held lighting contactor?

Product Line:
NEMA Contactors and Starters

Environment:
8903 Type LX Lighting Contactor

Answer:
Yes. First disconnect all power from the contactor. Latch by depressing the latch rod with an electrically insulated tool. To unlatch, depress the armature ring with an electrically insulated tool. Refer to the instruction bulletin provided with the contactor.