Does a shunt trip accessory on PowerPacT H, J, L, M, P, or R frame breakers take up any more space in an enclosure?
Issue:
Do the electrical accessories on PowerPacT H, J, L, M, P or R frame breakers take up additional room in a breaker enclosure?

Product Line:
PowerPact Molded Case Circuit Breakers

Resolution:
No. The shunt trips, auxiliary switches, alarm switches, overcurrent trip switches, and undervoltage trip accessories are installed inside of the breaker frame. Because of this, the breaker frame stays the same physical size whether it has an accessory or not.