Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Are oversized enclosures available for the LE1D or LE2D, IEC enclosed starters?
Issue:
Oversized enclosures for LE1D and LE2D

Product Line:
IEC Contactors and Starters

Environment:
Tesys D Enclosed Starters

Resolution:
We do not offer oversized enclosures.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings