What is the meaning of ''integral ground bus'' for I Line II busway?
Issue:
Integral ground bus for I Line II busway

Product Line:
I Line II Busway

Environment:
Application

Cause:
Clarification

Resolution:
IGB ( Integral Ground Buss) utilizes two 1/16 inch thick ground bus bars to form the housing top and bottom. This provides an integral 50% continuous current capacity ground path. Equally important, the two ground bus bars completely encircle the phase conductors and provide a very effective high level ground path for ground faults. This grounding system is different from the old type on internal, separate ground bus bar system.
*See attachments for further explanation

Schneider Electric USA

Attachment(s)
Busway Grounding 5600PN9101.pdf [567.42 KB]
Integral Ground understannding 2700HO9602 ().pdf [390.98 KB]
Page 15 - Integral Ground Bus.pdf [71.67 KB]