What is the power terminal lug data for the LC1D32 contactor?
Issue:
Wire size used on LC1D32 contactor.

Product Line:
Contactors and Starters-IEC

Environment:
Tesys D Contactors

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two # 14-6 AWG per terminal.
stranded cable w/cable end: One # 18-3/0 AWG per terminal, or two #14-#2 AWG per terminal.
solid cable: One #14-8 AWG or two # 10-8 AWG per terminal.