Issue:
What can I use to replace a GC100 / GC200 ground fault relay?
Product Line:
GC100
Resolution:
The GC100 Ground Fault relay is obsolete. It was replaced with a GC200 relay, which is now also obsolete and Schneider has no replacement.
If the GC100/GC200 was installed on a bolted pressure switch (Bolt-loc), then Services can replace it with a BPGF100.
If the GC100/GC200 was installed with a circuit breaker, then replace the breaker with one including integral ground fault protection. Services can do a retrofit to replace the breaker and the relay.
What can I use to replace a GC100 / GC200 ground fault relay?
Product Line:
GC100
Resolution:
The GC100 Ground Fault relay is obsolete. It was replaced with a GC200 relay, which is now also obsolete and Schneider has no replacement.
If the GC100/GC200 was installed on a bolted pressure switch (Bolt-loc), then Services can replace it with a BPGF100.
If the GC100/GC200 was installed with a circuit breaker, then replace the breaker with one including integral ground fault protection. Services can do a retrofit to replace the breaker and the relay.