Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the power terminal lug data for the LC1D80 and LP1D80 contactor?
Issue:
What is the clamp terminal wire size of LC1D80 and LP1D80 contactor?

Product Line:
IEC Contactors and Starters

Environment:
IEC TeSys D Contactor Accessories

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One #10-2 AWG or Two #10-4 AWG per terminal.
stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
solid cable: One #10-3 AWG or Two #10-2 AWG per terminal.

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings