Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the power terminal lug data for the LC1D115 and LC1D150 contactor?
Issue:
Power terminal lugs  for the LC1D115 and LC1D150 contactors

Product Line:
Tesys D Contactors and starters

Environment:
IEC contactors and starters

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One #8-250 kcmil or Two of the following per terminal: #8-1 AWG + #8-250 kcmil (one of each size range).
solid cable: One #8-250kcmil or Two of the following per terminal: #8-0 AWG + #8-250 kcmil (one of each size range).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings