Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do we have transformer sizing guide lines?
Issue:
Do we have transformer sizing guide lines?

Product Line:
Low voltage transformers.

Environment:
Products sold in the United States.

Cause:
Application.

Resolution:
A transformer is sized to accomodate the load it is serving plus any anticipated future loads, depending upon economic conditions For example, if you are feeding a 100 amp service panel, you may want to have the transformer able to supply 300 amps for load growth.


CTA-ID : 2017324

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings