What do the letters F, FB, H, HB or HF designate in SquareD/Schneider Electric Transformer catalog numbers?

Issue:
Temperature rise suffixes on Low Voltage Transformers

Product Line:
LV Transformers

Environment:
Products sold in North America

Cause:
Low Voltage Transformers have different insulation systems and temperature rise classifications

Resolution:
1. An F Suffix designates Class 180 insulation system with 115 deg C average temperature rise in the windings
2. An FB Suffix designates Class 180 insulation system with 80 deg C average temperature rise in the windings
3. An H Suffix designates Class 220 insulation system with 150 deg C average temperature rise in the windings
4. An HF suffix designates Class 220 insulation system with 115 deg C average temperature rise in the windings.
5. An HB suffix designates Class 220 insulation system with 80 deg C average temperature rise in the windings.

Insulation system is also often referred to as Insulation Class.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings