Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can a Buck-Boost Transformer be utilized on a 50hz system, even though the nameplate shows the Transformer to be rated for 60Hz?
Issue:
Buck Boost Transformers used on 50 Hz systems

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Cause:
50 Hz systems are used in many parts of the world

Resolution:
In some cases, yes.  If the induction levels of magnetic flux in the core of the Transformer resulting from the applied voltage at 50Hz do not exceed the unit`s acceptable induction levels, then it can be done.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings