What is the terminal wire data for the LK Neutral/Ground lugs(LK70AN, LK100AN, LK125AN, LK150AN, LK225AN and LK225ANHOM)?

Article available in these languages: Spanish

Issue:
Product Design Feature

Product Line:
QO and Homeline load centers

Cause:
Clarifying lug wire range

Resolution:
The LK70AN will accept a #12 - 2 AWG aluminum or #14-4 AWG copper wire.
The LK100AN will accept a #6 - 2/0 AWG AL or CU wire.
The LK125AN will accept a #14 - 2/0 AWG aluminum or copper wire.
The LK150AN will accept a #2 - 3/0 AWG aluminum or copper wire.
The LK225AN will accept a #4 AWG - 300 kcmil aluminum or copper wire. (For use in Series S, 150 - 225A QO load center OR Series S03 and below 150-225 A Homeline load centers
The LK225ANHOM will accept a #4 AWG - 300 kcmil AL/Cu wire. For use ONLY in Series S04, 150 -225A Homeline load centers


Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings