Masterpact ground fault breaker connected to modified differential ground fault (MDGF) system is failing secondary injection test with the full function test kit (FFTK)
Issue:
Ground Fault Test is failing using FFTK
Product Line:
Air Circuit Breaker
Resolution:
The full function test kit will only test residual equipment ground fault protection. Breakers configured for modified differential ground fault (MDGF) and ground source return (GSR) cannot be secondary injection tested. The solution is to rack breaker out of cradle/cell to isolate from the MDGF system. If it is a fixed breaker, then remove MDGF wiring from terminals M1, M2, and M3 while using the FFTK.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings